29 CFR 1926.404(b): Wiring design and protection: Branch circuits

29 CFR Part 1926 › § 1926.404 Wiring design and protection

The adopted requirement and the jurisdiction were confirmed from the official sources below. Verified from the official source.

Applicability shown for District of Columbia.

In plain language

On construction sites, temporary 120-volt, single-phase 15- and 20-amp receptacles in use by employees need GFCI protection, or the employer must run an assured equipment grounding conductor program.

Staff explanation. The official text below governs.

Official text

(b) Branch circuits—(1) Ground-fault protection—(i) General. The employer shall use either ground fault circuit interrupters as specified in paragraph (b)(1)(ii) of this section or an assured equipment grounding conductor program as specified in paragraph (b)(1)(iii) of this section to protect employees on construction sites. These requirements are in addition to any other requirements for equipment grounding conductors. (ii) Ground-fault circuit interrupters. All 120-volt, single-phase, 15- and 20-ampere receptacle outlets on construction sites, which are not a part of the permanent wiring of the building or structure and which are in use by employees, shall have approved ground-fault circuit interrupters for personnel protection. Receptacles on a two-wire, single-phase portable or vehicle-mounted generator rated not more than 5kW, where the circuit conductors of the generator are insulated from the generator frame and all other grounded surfaces, need not be protected with ground-fault circuit interrupters. (iii) Assured equipment grounding conductor program. The employer shall establish and implement an assured equipment grounding conductor program on construction sites covering all cord sets, receptacles which are not a part of the building or structure, and equipment connected by cord and plug which are available for use or used by employees. This program shall comply with the following minimum requirements: (A) A written description of the program, including the specific procedures adopted by the employer, shall be available at the jobsite for inspection and copying by the Assistant Secretary and any affected employee. (B) The employer shall designate one or more competent persons (as defined in § 1926.32(f)) to implement the program. (C) Each cord set, attachment cap, plug and receptacle of cord sets, and any equipment connected by cord and plug, except cord sets and receptacles which are fixed and not exposed to damage, shall be visually inspected before each day's use for external defects, such as deformed or missing pins or insulation damage, and for indications of possible internal damage. Equipment found damaged or defective shall not be used until repaired. (D) The following tests shall be performed on all cord sets, receptacles which are not a part of the permanent wiring of the building or structure, and cord- and plug-connected equipment required to be grounded: (1) All equipment grounding conductors shall be tested for continuity and shall be electrically continuous. (2) Each receptacle and attachment cap or plug shall be tested for correct attachment of the equipment grounding conductor. The equipment grounding conductor shall be connected to its proper terminal. (E) All required tests shall be performed: (1) Before first use; (2) Before equipment is returned to service following any repairs; (3) Before equipment is used after any incident which can be reasonably suspected to have caused damage (for example, when a cord set is run over); and (4) At intervals not to exceed 3 months, except that cord sets and receptacles which are fixed and not exposed to damage shall be tested at intervals not exceeding 6 months. (F) The employer shall not make available or permit the use by employees of any equipment which has not met the requirements of this paragraph (b)(1)(iii) of this section. (G) Tests performed as required in this paragraph shall be recorded. This test record shall identify each receptacle, cord set, and cord- and plug-connected equipment that passed the test and shall indicate the last date it was tested or the interval for which it was tested. This record shall be kept by means of logs, color coding, or other effective means and shall be maintained until replaced by a more current record. The record shall be made available on the jobsite for inspection by the Assistant Secretary and any affected employee. (2) Outlet devices. Outlet devices shall have an ampere rating not less than the load to be served and shall comply with the following: (i) Single receptacles. A single receptacle installed on an individual branch circuit shall have an ampere rating of not less than that of the branch circuit. (ii) Two or more receptacles. Where connected to a branch circuit supplying two or more receptacles or outlets, receptacle ratings shall conform to the values listed in Table K-4. (iii) Receptacles used for the connection of motors. The rating of an attachment plug or receptacle used for cord- and plug-connection of a motor to a branch circuit shall not exceed 15 amperes at 125 volts or 10 amperes at 250 volts if individual overload protection is omitted. Table K-4—Receptacle Ratings for Various Size Circuits

Source

Publication
Safety and Health Regulations for Construction
Edition
eCFR 2026-11-19
Publisher
OSHA (U.S. Department of Labor) via eCFR
Section
29 CFR 1926.404(b)
Page
Online regulation: cite by section and paragraph; there are no page numbers.
Effective
Not on file
Last verified
Nov 22, 2026
Rights
Public domain (U.S. Government work). Works of the U.S. Government are not subject to copyright (17 U.S.C. 105). Text is reproduced from the eCFR, which is an editorial compilation and not the official legal edition (the annual CFR and Federal Register are).

Verification history

  • Nov 22, 2026 · Section: Read in the official publication, verified · source
  • Nov 22, 2026 · Publication: Read in the official publication, verified · source
Report a problem

Educational information only. Building codes and licensing requirements vary by jurisdiction and may change. Verify requirements with the applicable authority having jurisdiction before beginning work.